Having sufficient knowledge of the latest and applicable design codes and standards enables a structural engineer to prepare cost-effective and safe design solutions for different structures. In essence, structures like concrete and steel buildings must be designed to resist the forces applied in various combinations/loading conditions. This is especially true for project sites where natural disasters such as storms/typhoons and earthquakes occur frequently.
Four (4) basic load cases are considered when designing steel buildings. The first two are predominantly applied along the gravity direction, while the succeeding loads are predominantly applied in the lateral direction. Further explanation of these basic load cases are as follows:
1. Dead Loads (D)
Dead loads are loads applied to the structure along the gravity direction. These include the self-weight of the structure (all permanent construction), and other materials permanently fastened onto the structure.
2. Live Loads (L)
Live loads are also applied along the gravity direction. These are loads are calculated depending on the structure’s occupancy. Live loads may vary at different locations of the structure. For example, the magnitude of the live load for an office space/room shall be different from that of the storage area of a particular building.
3. Wind Loads (W)
Wind loads are a combination of lateral and vertical loads applied to the contact surfaces of the building. Calculation of the wind load for a specific structure considers several factors. The structure’s geometry, the maximum wind speed at the project site, exposure category, gust effect, directionality and topography are just some of the major factors to be considered when designing buildings.
4. Earthquake Loads (E)
Earthquake/Seismic loads are forces calculated due to the seismic events the structure will be subjected to. Factors such as the nearest seismic source, the magnitude of the earthquake, soil type, and the type of seismic force-resisting system to be used are some of the factors to be considered in the calculation of the design earthquake loads for a structure.
The basic principle of structural design is to select the best section of a structural member that can safely and economically resist the loads applied to it. These loads include various combinations of gravity and lateral forces in accordance with the provisions of the referral code. A structural steel section is considered economical if it can resist loads while maintaining an optimum self-weight (usually expressed in mass per unit length). An optimized self-weight of the section implies that lighter steel sections are required to be fabricated, and effectively lowers the material cost. At present, there are two design philosophies that are being used when designing steel structures. These are the Allowable Stress Design (ASD) Method, and the Load and Resistance Factor Design (LRFD) Method.
In the Allowable Stress Design Method, the steel section to be selected shall have cross-sectional properties (i.e., area and moment of inertia) adequate to resist the maximum applied loads under a permissible value. Applied loads may be in the form of compressive or tensile axial forces, shear forces, bending moments, and torsion. Each form of the applied load is compared to a permissible value of sectional strength.
This permissible value is referred to as the Allowable Strength. The Allowable Strength is defined by taking the Nominal Strength of the steel section and dividing it by a Factor of Safety (FS).
The value of FS varies for different types of loading conditions. For example, the safety factor for bending moment capacity shall be different from the factor of safety for shear capacity of the section.
In the Load and Resistance Factor Design, the sectional strength of a member under failure conditions is considered. The design process under LRFD is done by taking the sum of applied service loads and multiplying it with an individual load factor for each load type. The factored loads are then applied to the structure. Member size selection is determined by calculating for the strength of the chosen steel section and multiplying it by a reduction factor. To illustrate this better, the working principle behind LRFD is expressed as follows:
Factored loads are usually greater than the service loads, thus making the load factors greater than 1.0. The factored strength is always less than the nominal strength of the steel section, thus making the resistance factor less than 1.0.
At this point, the discussion focused on the determination of the sectional strength of a structural member. Despite satisfying the strength requirements from the applied loads, serviceability is also an important criterion in determining the right design for a structure. Two of the most common factors to consider in serviceability are the member deflection and the story drift. Depending on the governing design code, the deflection criterion is satisfied by taking the maximum deflection of a structural member due to the applied loads, and comparing it with the allowable deflection prescribed in the code. The allowable deflection is expressed as a fraction of the member’s unsupported length. This fraction also varies depending on the load condition being considered (e.g., D only, L only, D plus L).
The second factor being considered when checking for serviceability is the drift of the structure. Drift is defined as the lateral displacement of the building when subjected to load combinations involving transient loads (wind and earthquake loads). In practice, the drift is calculated at the beam-column joints of the structure, per floor. The displacement of a joint on one story relative to one below it is called the inter-story drift.
For service load combinations involving wind loads, the permissible inter-story drift is valued as H/600 to H/400, where H is the story height. The permissible value is referred from Appendix CC (Serviceability Considerations) of ASCE 7-16 (Minimum Design Loads for Buildings and Other Structures).
For service load combinations involving earthquake/seismic loads, the seismic inter-story drift shall be not greater than 2.50% of the story height being considered for structures having a fundamental period of less than 0.70 s. For structures with a fundamental period of 0.70 s or greater, the seismic inter-story drift shall not be greater than 2.00% of the story height under consideration. The seismic drift is inelastic in nature due to the inelastic response of the seismic force-resisting system. The inelastic drift is calculated using the following equation:
Where Δm is the inelastic drift, R is the seismic response modification factor, and Δs is the elastic drift. The prescribed drift limits were based on studies that determine the tolerance of both structural and non-structural elements of a building against lateral displacements under seismic events.
It is important that safety and economics are considered when designing buildings of any material type (i.e., reinforced concrete, structural steel, or a combination of both). These two factors should go hand in hand to come up with efficient building designs of varying occupancies. Adequate sectional strength and serviceability limits as prescribed by the local/governing structural codes must be observed by the Structural Engineer, especially for areas frequently struck by natural disasters such as earthquakes and strong typhoons. Strict implementation of these referral design codes ensures the optimum performance of the building while maintaining the safety and welfare of the general public.
For expert assistance on your steel building structures requirement, contact our team. You may email us at info@escsteelstructures.com or visit our website https://www.escsteelstructures.com/ for further information
Whether you are advancing in healthcare or business, navigating key assessments effectively is essential for academic and professional growth. For students enrolled in Capella University's FlexPath programs or those seeking online course services, understanding the specifics of each assessment can significantly impact their success. This guide delves into critical assessments, offering insights to help you excel.
Understanding NHS FPX 6004 Assessment 1: Dashboard Metrics Evaluation
The NHS FPX 6004 Assessment 1 Dashboard Metrics Evaluation is designed to help healthcare professionals understand and analyze key performance indicators (KPIs) within a healthcare setting. In this assessment, students are tasked with evaluating a healthcare dashboard's metrics to determine areas that need improvement. It involves assessing data accuracy, relevance, and the effectiveness of the chosen metrics in…
Capella University's FlexPath format offers nursing students an innovative, self-paced learning experience that caters to their individual needs and schedules. This competency-based learning model is designed to allow students to progress through their coursework at their own pace, providing the flexibility to balance studies with professional and personal commitments. For nursing students, understanding the specifics of each assessment is key to success. Here’s a guide to navigating key assessments in the FlexPath nursing program.
What is Capella FlexPath Nursing?
Capella flexpath nursing provides an alternative to traditional learning formats by allowing students to complete courses as quickly as they can master the content. This format is particularly beneficial for working nurses who need a flexible schedule to accommodate their shifts and…
Nursing education is a challenging yet rewarding journey, especially for students pursuing advanced degrees such as the Doctor of Nursing Practice (DNP) or Master of Science in Nursing (MSN). At this level, academic expectations are significantly higher, with complex assessments, in-depth research, and dissertations forming a major part of the curriculum. From assignments like NURS FPX 8030 Assessment 5 to capstone projects such as NURS FPX 9904 Assessment 3, nursing students are required to demonstrate not only their clinical knowledge but also their ability to engage in critical thinking, research, and leadership. These assignments can be demanding, often pushing students to seek assistance from nursing dissertation writing services to manage their workload effectively.
For students navigating advanced nursing programs, assessments like NURS…
In today’s rapidly evolving educational landscape, online classes have become a crucial part of learning, especially for students in nursing programs. With the rise of digital platforms, the convenience and flexibility of studying from home have made it possible for students to continue their education amidst other responsibilities. However, online classes come with their own set of challenges, leading many students to seek assistance for managing their workload. The demand to do my online classes or seek help from online tutoring and writing services has increased, particularly for nursing students dealing with complex assessments such as NURS FPX 4060 Assessment 1.
Balancing coursework, clinical placements, and personal life can be daunting, leaving students overwhelmed. This is where external services play a…
fight